{"product_id":"ge-is200sttch2aba-thermocouple-terminal-board-mark-vie-simplex","title":"GE IS200STTCH2ABA | Thermocouple Terminal Board | Mark VIe Simplex","description":"\u003ch4\u003e\u003cspan\u003eProduct Overview\u003c\/span\u003e\u003c\/h4\u003e\n\u003cp\u003eThe \u003cspan\u003eGE IS200STTCH2ABA\u003c\/span\u003e is a high-performance \u003cspan\u003eThermocouple Terminal Board\u003c\/span\u003e used within the \u003cspan\u003eMark VIe control system\u003c\/span\u003e. This board is specifically designed to interface with \u003cspan\u003ethermocouple sensors\u003c\/span\u003e, providing \u003cspan\u003ecold junction compensation (CJC)\u003c\/span\u003e and serving as a key component in \u003cspan\u003etemperature monitoring\u003c\/span\u003e for turbine control.\u003c\/p\u003e\n\u003cp\u003eIt is intended for \u003cspan\u003eSimplex\u003c\/span\u003e applications, supporting \u003cspan\u003eup to 12 thermocouple inputs\u003c\/span\u003e. The \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e is designed to be used with the \u003cspan\u003eIS220PTCC I\/O Pack\u003c\/span\u003e, which digitizes the thermocouple signals and communicates the data to the \u003cspan\u003eMark VIe controller\u003c\/span\u003e via Ethernet.\u003c\/p\u003e\n\u003chr\u003e\n\u003ch4\u003e\u003cspan\u003eKey Technical Specifications\u003c\/span\u003e\u003c\/h4\u003e\n\u003col class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eSignal \u0026amp; Input Capacity\u003c\/span\u003e\u003cbr\u003eThe \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e provides excellent input capabilities for industrial temperature monitoring:\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eChannels\u003c\/span\u003e: Supports up to \u003cspan\u003e12 thermocouple inputs\u003c\/span\u003e per terminal board.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eThermocouple Types Supported\u003c\/span\u003e: Includes \u003cspan\u003eType E, J, K, S\u003c\/span\u003e, and \u003cspan\u003eT\u003c\/span\u003e thermocouples, as well as \u003cspan\u003emillivolt (±100 mV)\u003c\/span\u003e inputs for additional flexibility.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eCold Junction Compensation (CJC)\u003c\/span\u003e: Features \u003cspan\u003etwo on-board thermistors\u003c\/span\u003e that ensure accurate temperature readings by compensating for the ambient temperature at the terminal block.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003ePhysical \u0026amp; Mechanical Specifications\u003c\/span\u003e\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eConnection Type\u003c\/span\u003e: Features \u003cspan\u003etwo fixed terminal blocks\u003c\/span\u003e, each supporting \u003cspan\u003e24 terminals\u003c\/span\u003e, which can accept wire sizes ranging from \u003cspan\u003eAWG #18 to #14\u003c\/span\u003e.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eMounting\u003c\/span\u003e: Designed for \u003cspan\u003evertical mounting\u003c\/span\u003e in a \u003cspan\u003eMark VIe cabinet\u003c\/span\u003e or on a \u003cspan\u003eDIN-rail\u003c\/span\u003e for easy installation in industrial environments.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eI\/O Pack Compatibility\u003c\/span\u003e: The \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e is designed to work seamlessly with the \u003cspan\u003eIS220PTCC I\/O pack\u003c\/span\u003e via a \u003cspan\u003e37-pin D-type connector\u003c\/span\u003e.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eHardware Features\u003c\/span\u003e\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eSimplex Configuration\u003c\/span\u003e: Ideal for \u003cspan\u003eSimplex\u003c\/span\u003e setups, this terminal board supports one I\/O pack for applications where redundancy is not required. For \u003cspan\u003eTriple Modular Redundancy (TMR)\u003c\/span\u003e systems, a different terminal board, such as the \u003cspan\u003eIS200TBTCH\u003c\/span\u003e, would typically be used.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eNoise Suppression\u003c\/span\u003e: The board integrates \u003cspan\u003ehigh-frequency decoupling and surge protection\u003c\/span\u003e for each input channel to prevent interference and ensure accurate signal processing.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eID Chip\u003c\/span\u003e: The \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e includes a \u003cspan\u003eBoard ID\u003c\/span\u003e serial EEPROM, allowing the I\/O pack to automatically identify the board type and revision, simplifying installation and configuration.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/ol\u003e\n\u003chr\u003e\n\u003ch4\u003e\u003cspan\u003eSystem Architecture Comparison\u003c\/span\u003e\u003c\/h4\u003e\n\u003ctable class=\"w-fit min-w-(--thread-content-width)\" width=\"NaN\"\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003cth\u003e\u003cspan\u003eFeature\u003c\/span\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cspan\u003eIS200STTCH2ABA (Board)\u003c\/span\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cspan\u003eIS230SNTCH4A (Board Variation)\u003c\/span\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003ePrimary Role\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003eSimplex thermocouple termination\u003c\/td\u003e\n\u003ctd\u003eSpecialized thermocouple termination\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eI\/O Pack Compatibility\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cspan\u003eIS220PTCC\u003c\/span\u003e series\u003c\/td\u003e\n\u003ctd\u003e\n\u003cspan\u003eIS220PTCC\u003c\/span\u003e series\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eCold Junction Compensation\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e2 on-board thermistors\u003c\/td\u003e\n\u003ctd\u003e2 on-board thermistors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003eRevision Codes\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cspan\u003eH2ABA\u003c\/span\u003e (specific revision)\u003c\/td\u003e\n\u003ctd\u003e\n\u003cspan\u003eH4A\u003c\/span\u003e (updated style)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003chr\u003e\n\u003ch4\u003e\u003cspan\u003eEnvironmental Specifications\u003c\/span\u003e\u003c\/h4\u003e\n\u003cp\u003eThe \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e is built to endure challenging industrial environments with the following environmental limits:\u003c\/p\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eOperating Temperature\u003c\/span\u003e: \u003cspan\u003e-30°C to +65°C\u003c\/span\u003e (—22°F to +149°F) for reliable performance in a wide range of conditions.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eStorage Temperature\u003c\/span\u003e: \u003cspan\u003e-40°C to +85°C\u003c\/span\u003e to accommodate temperature fluctuations during shipping or long-term storage.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eRelative Humidity\u003c\/span\u003e: Operates within \u003cspan\u003e5% to 95% non-condensing\u003c\/span\u003e humidity levels.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003ePollution Degree\u003c\/span\u003e: Rated for \u003cspan\u003ePollution Degree 2\u003c\/span\u003e, suitable for standard industrial indoor environments.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003chr\u003e\n\u003ch4\u003e\u003cspan\u003eApplications\u003c\/span\u003e\u003c\/h4\u003e\n\u003cp\u003eThe \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e is ideal for applications requiring reliable temperature measurement and control, particularly in \u003cspan\u003epower generation\u003c\/span\u003e and \u003cspan\u003eturbine systems\u003c\/span\u003e. This terminal board plays a critical role in:\u003c\/p\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eTurbine Control\u003c\/span\u003e: Provides accurate temperature feedback from thermocouples to help manage the operation of steam and gas turbines.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eIndustrial Process Control\u003c\/span\u003e: Used in environments requiring precise temperature data for machinery and equipment protection.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cspan\u003eTemperature Monitoring\u003c\/span\u003e: Ideal for systems that need to monitor high-temperature processes for safety and efficiency.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003chr\u003e\n\u003ch4\u003e\u003cspan\u003eFAQ\u003c\/span\u003e\u003c\/h4\u003e\n\u003cp\u003e\u003cspan\u003eQ: What is the maximum number of thermocouple inputs supported by the IS200STTCH2ABA?\u003c\/span\u003e\u003cbr\u003e\u003cspan\u003eA:\u003c\/span\u003e The \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e supports \u003cspan\u003eup to 12 thermocouple inputs\u003c\/span\u003e, allowing for comprehensive temperature monitoring in industrial systems.\u003c\/p\u003e\n\u003cp\u003e\u003cspan\u003eQ: How does cold junction compensation (CJC) work on this board?\u003c\/span\u003e\u003cbr\u003e\u003cspan\u003eA:\u003c\/span\u003e The \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e has \u003cspan\u003etwo on-board thermistors\u003c\/span\u003e that automatically compensate for ambient temperature fluctuations, ensuring accurate thermocouple readings.\u003c\/p\u003e\n\u003cp\u003e\u003cspan\u003eQ: What types of thermocouples can the IS200STTCH2ABA handle?\u003c\/span\u003e\u003cbr\u003e\u003cspan\u003eA:\u003c\/span\u003e The board supports common thermocouple types including \u003cspan\u003eType E\u003c\/span\u003e, \u003cspan\u003eJ\u003c\/span\u003e, \u003cspan\u003eK\u003c\/span\u003e, \u003cspan\u003eS\u003c\/span\u003e, \u003cspan\u003eT\u003c\/span\u003e, and millivolt inputs for custom signal ranges (±100 mV).\u003c\/p\u003e\n\u003cp\u003e\u003cspan\u003eQ: Can the IS200STTCH2ABA be used in redundant systems?\u003c\/span\u003e\u003cbr\u003e\u003cspan\u003eA:\u003c\/span\u003e While the \u003cspan\u003eIS200STTCH2ABA\u003c\/span\u003e is designed for \u003cspan\u003eSimplex configurations\u003c\/span\u003e, it is not suited for \u003cspan\u003eTriple Modular Redundancy (TMR)\u003c\/span\u003e systems. For redundancy, consider using the \u003cspan\u003eIS200TBTCH\u003c\/span\u003e terminal board instead.\u003c\/p\u003e","brand":"GE","offers":[{"title":"Default Title","offer_id":44092531802211,"sku":"IS200STTCH2ABA（IS230SNTCH4A）","price":180.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0549\/2775\/3315\/files\/IS200STTCH2ABA_IS230SNTCH4A_-1.jpg?v=1774941428","url":"https:\/\/precisemodule.com\/products\/ge-is200sttch2aba-thermocouple-terminal-board-mark-vie-simplex","provider":"Precise Module Ltd.","version":"1.0","type":"link"}