Honeywell
📢 100% genuine, extensive in-stock inventory, fast shipping!
Honeywell 8C-PDILAI Digital Input Module
Honeywell 8C-PDILAI Digital Input Module
Manufacturer: Honeywell
-
Product No.: 8C-PDILAI
Condition:in Stock
Product Type: Digital Input Module
-
Product Origin: USA
Payment:T/T, Western Union
-
Weight: 270g
Shipping port: Shanghai/Yiwu/Shenzhen
Warranty: 12 months
Share
Honeywell 8C-PDILAI Digital Input Module
The Honeywell 8C-PDILAI, also cataloged as the 51454471-175 digital input module, operates as a dedicated hardware component for discrete signal acquisition within Experion PKS Series 8 and C300 distributed control systems.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 8C-PDILAI |
| Brand | Honeywell |
| Origin | USA |
| Weight | ~270 g |
| Dimensions | Standard Series 8 I/O form factor |
| Operating Temp | 0 deg C to +60 deg C (storage -40 to +70 deg C) |
| Power Consumption | 95 mA @ 24 VDC |
| Channel Capacity | 32 digital input channels |
| Nominal Voltage | 24 VDC (range 18–30 VDC) |
| Input Impedance | 4.2 kΩ |
| Isolation | 1000 VAC RMS / ±1500 VDC optical isolation |
| ON Threshold | ≥13 VDC / ≥3 mA |
| OFF Threshold | ≤5 VDC / ≤1.2 mA |
| Environmental Protection | G3 conformal coating |
| Hazardous Area Ratings | Class I, Div 2, Groups A–D, T4 |
| ATEX Certification | II 3G Ex nA IIC T4 Gc (Sira 14ATEX4109X) |
| Hot-Swap Support | Yes |
Channel-to-Channel Isolation
The 8C-PDILAI employs optical galvanic isolation rated at 1000 VAC RMS or ±1500 VDC, ensuring deterministic separation between field wiring and system logic. This design prevents cross-talk and maintains stable acquisition across 32 discrete channels. The G3 conformal coating enhances durability against dust, moisture, and corrosive contaminants, while hot-swap capability allows module replacement under live system power without disrupting terminal connections.
Frequently Asked Questions
Q: Can the 8C-PDILAI be replaced while the system is energized? A: Yes, the module supports hot-swap replacement under live system power, minimizing downtime.
Q: How does the module handle hazardous area compliance? A: It is certified for Class I, Division 2 environments and ATEX II 3G Ex nA IIC T4 Gc, ensuring safe operation in industrial hazardous zones.
Q: What is the minimum ON sense requirement? A: The ON state requires at least 13 VDC and 3 mA input current to register as active.
Field Installation Guidelines
- Mount the module securely in the Series 8 chassis with proper alignment to avoid connector damage.
- Use shielded cabling for input wiring to reduce EMI.
- Maintain separation between high-voltage and low-voltage circuits.
- Verify polarity and voltage range compliance (18–30 VDC).
- Observe environmental limits and ensure adequate ventilation for operation up to 60 deg C.
- Confirm diagnostic LEDs during commissioning to validate input states.