Honeywell 8C-TAIDB1 Termination Assembly

Honeywell 8C-TAIDB1 Termination Assembly

  • Manufacturer: Honeywell

  • Product No.: 8C-TAIDB1

  • Condition:in Stock

  • Product Type: Termination Assembly

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 560g

  • Shipping port: Shanghai/Yiwu/Shenzhen

  • Warranty: 12 months

Honeywell 8C-TAIDB1 Termination Assembly

The Honeywell 8C-TAIDB1 (8C-TAIDB1 Termination Assembly) operates as a dedicated signal termination and field interface component for analog input acquisition within Honeywell control systems. Designed for use with the 8C-PAIH54 Analog Input with HART module, the assembly provides field signal conditioning, channel termination, redundant connectivity, and support for both voltage and current input measurements.

Hardware Specifications

Parameter Specification
Model 8C-TAIDB1 (51307133-175)
Brand Honeywell
Origin Not specified in supplied documentation
Product Type Termination Assembly
Form Factor 12-Inch Redundant
Channel Capacity 16 channels
Channel Configuration Single-ended or differential
Compatible Module 8C-PAIH54 Analog Input with HART
Input Signal Range 1 to 5 VDC
Current Input Range 4-20 mA via integrated 250 Ohm resistor
Maximum Input Voltage ±30 VDC
A/D Resolution 16-bit
Module Current Draw Approximately 310 mA at 24 VDC
Supply Voltage 24 VDC
Loop Scan Rate 50 ms per channel
Accuracy @ 23.5 deg C ±0.075% FS
Accuracy (0 to 60 deg C) ±0.15% FS
Common Mode Rejection Ratio 70 dB (500 Ohm imbalance)
Normal Mode Rejection Ratio 19 dB at 60 Hz
Crosstalk Isolation -60 dB
Environmental Protection G3 conformal coating
Operating Temp 0 to 60 deg C
Storage Temp -40 to 85 deg C
Weight Not specified in supplied documentation
Dimensions 12-Inch redundant assembly
Power Consumption Approximately 7.44 W

4-20 mA HART Loop Signal Processing

The 8C-TAIDB1 is intended for operation with the Honeywell 8C-PAIH54 Analog Input with HART module. The assembly supports direct acquisition of 1-5 VDC signals and 4-20 mA process loops through integrated 250 Ohm conversion resistors. This arrangement enables analog process measurements and HART communication signals to be transmitted through a common field wiring infrastructure. The termination assembly serves as the field interface layer between process instrumentation and the associated analog input electronics.

Frequently Asked Questions

Q: How many field channels can the 8C-TAIDB1 support?
A: The termination assembly supports up to 16 channels and may be configured for either single-ended or differential signal operation.

Q: Is direct 4-20 mA input wiring supported?
A: Yes. The assembly supports 4-20 mA signals through an integrated 250 Ohm resistor network, allowing conversion to the corresponding voltage input range required by the associated analog input module.

Q: What environmental protection is provided for industrial installations?
A: The assembly includes G3 conformal coating to improve resistance against corrosive and industrial environmental conditions.

Field Installation Guidelines

  • Verify compatibility with the 8C-PAIH54 Analog Input with HART module before installation.

  • Confirm field wiring assignments for single-ended or differential channel configuration prior to termination.

  • Route analog signal cables separately from motor power and switching circuits.

  • Maintain shield continuity and grounding practices consistent with site instrumentation standards.

  • Verify loop polarity before connecting 4-20 mA transmitters.

  • Avoid exceeding the specified ±30 VDC maximum input limitation.

  • Inspect termination points for secure field wiring before energizing the system.

  • Validate channel scaling and HART communication performance during commissioning.