Honeywell MC-TAIH02 51304453-150 High Level Analog Input/STI FTA

  • Manufacturer: Honeywell

  • Product No.: MC-TAIH02 51304453-150

  • Condition:in Stock

  • Product Type: Analog Input/STI FTA

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 300g

  • Shipping port: Shanghai/Yiwu/Shenzhen

  • Warranty: 12 months

Honeywell MC-TAIH02 51304453-150 High Level Analog Input/STI FTA

The Honeywell MC-TAIH02 51304453-150, also cataloged as the MC-TAIH02 High Level Analog Input/STI FTA, operates as a dedicated hardware component for field signal termination and conditioning within Experion PKS and TDC 3000 DCS platforms.

Hardware Specifications

Parameter Specification
Model MC-TAIH02 / 51304453-150
Brand Honeywell
Origin United States
Weight 0.3 kg
Dimensions Standard FTA board layout (304 mm x 122 mm approx.)
Operating Temp -40 to +70 deg C
Power Consumption 24 VDC system power supply
Number of Channels 16 channels
Signal Types High-Level Analog Input (4-20 mA, 1-5 VDC) / STI
System Compatibility Honeywell TDC 3000, Experion PKS (MC-PAIH03 IOP)
Cable Interface Multi-conductor FTA interface cable to I/O Processor

Process Control and 4-20 mA HART Loop Protocol Execution

Field Termination Assemblies (FTAs) provide pass-through signal routing and current loop power distribution for 16-channel analog input cards. The board maintains 4-20 mA HART loop protocol signal integrity by filtering high-frequency noise while allowing bi-directional digital frequency-shift keying (FSK) communication between field transmitters and process controllers. Integrated channel-to-channel isolation networks prevent field wiring noise, ground potential differences, and common-mode voltage spikes from corrupting central I/O processor calculations.

Frequently Asked Questions

Q: Can the MC-TAIH02 FTA provide loop power to 2-wire field transmitters?

A: Yes. When connected to a 24 VDC power distribution source, the FTA routes system loop power directly to the individual field terminals for 2-wire 4-20 mA transmitters.

Q: Is hot-swappable replacement supported for the multi-conductor cable connecting to the MC-PAIH03 IOP?

A: Yes. The interface cable can be disconnected and reconnected while the system is powered, provided field loop connections are safely monitored during the maintenance window.

Field Installation Guidelines

  • Mount the FTA securely onto standard DIN-rail assemblies inside the termination cabinet, verifying that grounded metal DIN clips make solid electrical contact with the panel backplate.
  • Strip field signal wire insulation to recommended lengths and torque screw terminal connectors to specified rating (typically 0.5 to 0.6 Nm) to avoid loose wire faults.
  • Route 24 VDC redundant power wiring separately from high-level analog signal cables to prevent inductive coupling and transient noise propagation.
  • Ensure shield drain wires from 4-20 mA field cables are tied to the cabinet single-point ground bar and left floating/insulated at the field instrument enclosure.
  • Connect the multi-conductor interface cable between the FTA terminal socket and the corresponding MC-PAIH03 I/O processor board, ensuring side locking clips fully engage.